EasyManua.ls Logo

Basler BE1-11g - Page 534

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
522 9424200994 Rev N
Step 3: Increase the phase voltage source until OUT4 begins pulsing. This should occur immediately
but reaches the maximum width/interval period when the source is raised above approximately
74.48 V.
Step 4: Pulse width at the maximum period should be verified by measuring the elapsed time between
when the contact closes and when it opens. The measured length should be 5 s ±33.3 ms.
Step 5: Pulse interval should be verified by measuring the elapsed time between when a contact opens
and when it closes. The measured length should be 10 s ±50 ms.
Step 6: Decrease the phase voltage source until OUT5 begins pulsing. This should occur immediately
but reaches the maximum width/interval period when the source is raised above approximately
58.89 V.
Step 7: Repeat Steps 4 and 5.
Step 8: (Optional) Repeat Steps 2 through 7 for Settings Group 1, 2, and 3.
Frequency Raise/Lower Proportional Output Verification
Step 1: Use BESTCOMSPlus to monitor the status of OUT2 (Lower) and OUT3 (Raise).
Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13
(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn, 0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT2 and OUT3
should be open.
Step 3: Slowly increase the frequency of the phase voltage source until OUT2 begins pulsing. This
should occur immediately but reaches the maximum width/interval period when the source is
raised above approximately 60.4 Hz.
Step 4: Pulse width should be verified by measuring the elapsed time between when the contact closes
and when it opens. The measured length should be 10 s ±50 ms.
Step 5: Pulse interval should be verified by measuring the elapsed time between when a contact opens
and when it closes. The measured length should be 5 s ±33.3 ms.
Step 6: Decrease the phase voltage source until OUT5 begins pulsing. This should occur immediately
but reaches the maximum width/interval period when the source is lowered below approximately
59.6 Hz.
Step 7: Repeat Steps 4 and 5.
Step 8: (Optional) Repeat Steps 2 through 5 for Settings Group1, 2, and 3.
Breaker Close Attempts/Sync Fail Activation Delay Verification
Step 1: Use BESTCOMSPlus to verify the settings in Table 236 and set the logic in Figure 316 above.
Step 2: Prepare to monitor the status of OUT1 (Close Breaker) and OUT8 (Sync Fail).
Step 3: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13
(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn, 0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral).
Step 4: Connect a contact sensing input to terminals B3 (IN2+) and B4 (IN2-).
Step 5: Apply contact sensing voltage to IN2 to initiate a close attempt and cause OUT1 to close.
CAUTION: Applying voltage above the capabilities of the BE1-11g power supply can cause
irreversible damage to the BE1-11g. Consult the Specifications chapter for more information on
contact input voltage ranges.
Step 6: OUT1 should close two more times for a total of three close attempts. OUT8 should close
approximately 5 seconds after the third close attempt.
Step 7: (Optional.) Repeat Steps 2 through 6 for Settings Group 1, 2, and 3.
Synchronizer (25A) Test BE1-11g

Table of Contents

Related product manuals