9424200994 Rev N 577
59X - Auxiliary Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy.................................................................... ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98% ±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy.................................................................... ±1.5% or ±4 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy.................................................................... ±8% or ±4 cycles, whichever is greater
Refer to the Time Curve Characteristics chapter
for information on available timing curves.
60FL - Fuse Loss
Time Delay ................................................................ Fixed at 50 ms
62 - Logic Timers
Modes ........................................................................ Pickup/Dropout, One-Shot/Non-Retriggerable,
One-Shot/Retriggerable, Oscillator, Integrating
Timer, Latched
Setting Range ........................................................... 0 to 9,999,000 ms
Accuracy.................................................................... ±0.5% or ±12 ms, whichever is greater
67/67N - Directional Current and Polarization Protection
Modes ........................................................................ Forward, Reverse, Non-directional
Maximum Torque Angle ............................................ 0 to 359.9°
Polarization Methods
Zero Sequence Current Polarization (IG)
Negative Sequence Polarization (Q)
Zero Sequence Polarization (V)
VOIN - Calculated Zero Sequence Voltage compared to Calculated Zero Sequence Current.
VOIG - Calculated Zero Sequence Voltage compared to Measured Ground Current.
VXIN - Measured 3V0-VX Input compared to Calculated Zero Sequence Current.
VXIG - Measured 3V0-VX Input compared to Measured Ground Current.
78OOS - Out of Step Protection
Reverse/Forward Reach
Setting Range ........................................................... 0 to 500
Accuracy
5 Ampere CT .......................................................... ±5% or ±0.4 , whichever is greater from 100 to 100
1 Ampere CT .......................................................... ±5% or ±0.4 , whichever is greater from 500 to 500
Blinder A/Blinder B Offset
Setting Range ........................................................... 0 to 500
Accuracy
5 Ampere CT .......................................................... ±5% or ±0.4 , whichever is greater from 100 to 100
1 Ampere CT .......................................................... ±5% or ±0.4 , whichever is greater from 500 to 500
BE1-11g Specifications - 25 Hz Operation