9424200994 Rev N 53
Figure 43. Sync-Check Settings Screen
Table 13. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Voltage Difference
0 or 1 to 50
1
percent
0
Slip Angle
1 to 99
1
degrees
10
Slip Frequency
0.01 to 0.5
0.01
hertz
0.01
Source Freq > Destination Freq
Disabled or Enabled
n/a
n/a
Disabled
Angle Compensation
0 to 359.9
0.1
degrees
0
25 VM Live Voltage
0 or 10 to 90
1
percent
0
25 VM Dead Voltage
0 or 10 to 90
1
percent
0
25 VM Drop Out Delay
0 or 50 to 60,000
varies
milliseconds
50
25 Voltage Monitor Logic
0 = Disabled
123, 12, 13, 23
n/a n/a 0
BE1-11g Sync-Check (25) Protection