EasyManuals Logo

Basler BE1-11g User Manual

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
9424200994 Rev N 67
Figure 49. Overvoltage Settings Screen
Table 20. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled,
One of Three,
Two of Three,
or Three of Three
n/a n/a Disabled
Pickup
0 or 1 to 300
0.1
volts
0
Timing Mode
Definite or Inverse
n/a
n/a
Definite
Time Delay (Definite Timing)
50 to 600,000
varies
milliseconds
50
Time Dial (Inverse Timing)
0 to 9.9
0.1
units
0
BE1-11g Phase Overvoltage (59P) Protection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler BE1-11g and is the answer not in the manual?

Basler BE1-11g Specifications

General IconGeneral
BrandBasler
ModelBE1-11g
CategoryRelays
LanguageEnglish

Related product manuals