72 9424200994 Rev N
Table 23. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode*
Disabled,
3V0, V1, V2,
Vx Fundamental,
Vx Third Harmonic
n/a n/a Disabled
Pickup
0 or 1 to 150
0.1
volts
0
Timing Mode
Definite or Inverse
n/a
n/a
Definite
Time Delay (Definite Timing)
50 to 600,000
varies
milliseconds
50
Time Dial (Inverse Timing)
0 to 9.9
0.1
units
0
* To use 3V0, V1, or V2, the VTP connection cannot be single-phase.
Auxiliary Overvoltage (59X) Protection BE1-11g