9424200994 Rev N 83
Setting
Range
Increment
Unit of Measure
Default
Voltage Inhibit
0 or 15 to 250
0.1
volts*
20
81ROC
Over Frequency Inhibit
15 to 70 Hz
0.01
hertz
61
Under Frequency Inhibit
15 to 70 Hz
0.01
hertz
59
Negative Sequence Inhibit
0 to 99
1
percent
20
* Phase-to-phase and phase-to-neutral settings depend on the Phase VT and Aux VT connection
settings. Refer to the Configuration chapter for more information on these settings.
BE1-11g Frequency (81) Protection