EasyManua.ls Logo

Baumuller BM4400 - Requirements for the Motor Temperature Sensors

Baumuller BM4400
360 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Requirements for the motor temperature sensors
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07 Baumüller Nürnberg GmbH
170
of 358
7.8
In order to have EMC-compliant and problem-free use within the framework of the legis-
lation, the following aspects must be taken into account.
In case of any questions, please contact Sales or the Applications department of
Baumüller Nürnberg GmbH.
m Only use Baumüller motor cables and Baumüller components.
m Use suitable mains
filters from Baumüller Nürnberg GmbH.
m M
ount all components on a single mounting plate with a continuously good electrically-
conductive surface (e.g. galvanized steel plate).
m Ke
ep the ground connection device/ground plate as short as possible (< 30 cm) , using
fine-stranded cables with a large cross-section (>10 mm
2
).
m When installing,
be sure to follow the correct sequence:
power supply system - fuse - filter - choke - (ferrite core) - BM
4400, BM4600, BM4700
- (motor filter) - motor.
m En
sure that the motor cable is continuous, without interruption.
Do not interrupt motor cables with terminals, co
ntactors or fuses, for example.
m Ro
ute the cables directly on the surface of the grounded mounting plate.
(smallest possible effec
tive aerial height).
m Wh
en routing in parallel, maintain a minimum clearance of 20 cm between signal and
control cables vis-à-vis the power cables.
m Cro
ss cables with different EMC categories (signal cables - supply cables or motor ca-
bles) only in a 90° angle.
m Contact the
major cable shield when laying cables through walls, which separate dif-
ferent EMC areas.
m Co
ntact all the cable’s shields on both sides surface-to-surface and also well-conduc-
tive with ground.
7.8 Requirements for the motor temperature sensors
Type Additional requirements: Isolation
KTY84 - SELV/PELV
MSKL
1)
(PTC) R = 1 k at T
threshold
, I
max
< 2 mA SELV/PELV
To protect the motor against not permitted overheating, a motor temperature sensor can
b
e connected to the b maXX device. The device switches off of the motor when a settable
threshold temperature has been exceeded.
1)
Motor protection resistor (PTC) as per DIN 44080-082
NOTE!
The motor temperature sensor should be installed in such a manner that „safe elec-
trical separation“ is ensured. The motor temperature sensors integrated into
Baumüller motors meet these requirements. If third-party motors are connected, the
proprietor must ensure that the temperature sensors used in the motor of a third-party
manufacturer motor comply with the „safe electrical separation“ function.

Table of Contents

Related product manuals