EasyManua.ls Logo

Baumuller BM4400 - Cabling

Baumuller BM4400
360 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cabling
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07 Baumüller Nürnberg GmbH
268
of 358
11.1
11.1 Cabling
11.1.1 Cables power supply-device
Device Number of wires x
cross section
1)
Connection to device
3)
Maximum length
2)
BM441X 4 x 0.5 to 2.5 mm
2
(AWG 16 - 12)
flexible cable
w
ith/without wire end ferrule
(plug-in terminal)
power supply to mains filter:
user-defined
mains filter to power choke/
device:
max. 30 cm
BM442X 4 x 0.5 to 4 mm
2
(AWG 24 - 10)
flexible cable with wire end ferrule
(
screw terminal)
BM4432
BM4433
BM4434
4 x 0.5 to 10 mm
2
(AWG 20 - 6)
flexible cable with wire end ferrule
(
screw terminal)
BM4435
4)
4 x 16 mm
2
63 A-fuses must be provided
for
the cable protection and a
cable with 16 mm
2
cross sec-
tion must be used.
pin-cable-lugs according to DIN
46230
The terminals at the BM4435 are provided for
cross sections up to 10 mm
2
, therefore at the
BM4435 pin-cable-lugs according to DIN
46230 must be used.
BM4632 4 x 25 mm
2
63 A-fuses must be provided
for
the cable protection and a
cable with 25 mm
2
cross sec-
tion must be used.
flexible cable with wire end ferrule
(screw terminal)
BM444X
BM464X
4 x 16 to 50 mm
2
(AWG 6 -0)
flexible cable with wire end ferrule
(
screw terminal)
BM445X
BM465X
BM475X
4 x 25 to ca. 185 mm
2
cable lug max. width: 25 mm
(current bar)
5)
BM446X
BM466X
BM476X
cable lug max. width: 35 mm
(current bar)
6)
BM447X
BM477X
max. 4 cables with
(4 x 95 mm
2
)
max. 2 cables with
(4 x 185 mm
2
)
cable lug max. width: 25 mm or
35 mm (current bar)
7)
1)
Possible cross section
For UL conform machines/installations you must use
UL certified circuit cables.
2)
The length of the cable between mains filter and power supply is not of importance for the compliance to the EMC regulation.
3)
The installing of the cables is user-defined.
4)
NOTE BM4435, BM4635
The BM4435 has an input current of 53 A, the appropriate mains filter (BFN3-1-56-001) has a rated current of 53 A, too.