Operating requirements
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07 Baumüller Nürnberg GmbH
52
of 358
3.3
3.3.2 Requirements to the energy supply
Supply system
(see ZSyst
em typesfrom
page 51)
BM44XX - XTX
6)
BM46XX - XTX
6)
BM47XX - XTX
6)
Industrial system with a
direct grounded neutral point or with a
low impedant grounded neutral point
(TN system or TT system)
BM44XX - XIX
BM46XX - XIX
BM47XX - XIX
Industrial system with a
gr
ounded star point (IT-system), which has no
or high impedance
Industrial system with direct or low impedance
ea
rthed phase junctions (grounded delta wye)
Inductance
(sum of power supply
indu
ctance and choke
inductance)
BM441X, BM442X min. u
k
= 0.4 % max. u
k
= 4 %
BM4426, BM443X, BM444X,
BM463X, BM464X
min. u
k
= 2.4 % max. u
k
= 4 %
BM445X, BM465X, BM475X,
BM
446X, BM466X, BM476X,
BM447X, BM477X
min. u
k
= 4 % max. u
k
= 6 %
Rated supply voltage/-frequency
1) 2)
(U
AC
) device
3 x 400 V
50/60 Hz
Absolute minimum supply voltage device
1) 2)
(U
AC
)
Absolute maximum supply voltage device
1) 2)
(U
AC
)
3 x 207 V
/ 50/60 Hz
3 x 528 V / 50/60 Hz
Absolute minimum frequency
5)
Absolute maximum frequency
5)
47 Hz
63 Hz
Overvoltage category
EN 61800-5-1, chapter. 4.3.6
III
Harmonics (power supply voltage)
EN 61800-3, chapter 5.2.1, chapter 3
THD
U
b 12 %
Unbalanced power supply voltage
EN 61000-2-4, Tab. 1, class 3
max. 3 %
Commutating dips
EN 61800-3, chapter 5.2.1, class 3
Depth of dip < 40 %, area < 250 % x degrees
Voltage dips
EN 61800-3:2004 and A1:2012
10 % to 80 %
1)
Voltage variations/-fluctuations
EN 61200-2-4, class 3
+/-10 %
+10 % to -15 % at a period of b 1 min
Short Circuit Current Rating (SCCR)
4)
65 kA
Rated supply voltage /
-frequency (U
AC
) fan
7)
BM444X-S/A, BM445X-S/A,
BM446X-S/A,
BM464X-S/A, BM465X-S/A,
BM466X-S/A
230 V 10 %
50/6
0 Hz
BM447X-A 3 x 400 V 10 %
50/6
0 Hz
Control voltage
3)
(U
DC
)
following EN 61131-2:1994, table 7
+ 24 V -15 % / +20 %
/ supply system