Cabling
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07 Baumüller Nürnberg GmbH
270
of 358
11.1
11.1.2 Cables device-motor
Device Number of wires x
cross section
1)
Maximum length
2)3)
Connection to device
BM441X 4 x (1 to 2.5 mm
2
)
(AWG 16 - 12)
100 m flexible cable with/without wire
end ferrule (plug-in terminal)
BM442X 4 x (2 to 4 mm
2
)
(AWG 24 -10)
1.5 to 2,5 mm
2
: 100 m
from 4 mm
2
: 60 m
flexible cable with wire end ferrule
(s
crew terminal)
BM443X
BM4632
4 x (4 to 16 mm
2
)
(AWG 20 - 4)
60 m
BM444X
BM464X
4 x (16 to 50 mm
2
)
(AWG 6 - 0)
up to 25 mm
2
: 60 m
from 35 mm
2
: 50 m
BM445X
BM465X
BM475X
4 x (20 to ca. 185 mm
2
) up to 50 mm
2
: 50 m
> 50 mm
2
: 15 m
cable lug max. width:
25 mm (current bar)
4)
BM446X
BM466X
BM476X
cable lug max. width:
35 mm (current bar)
5)
BM447X
BM477X
max. 4 cables each with
(4 x 95 mm
2
)
max. 4 cables each with
(2 x 185 mm
2
)
at 95 mm²: 15 m
at 185 mm²: 30 m
cable lug max. width: 25 mm or 35
mm
(current bar)
6)
1)
Possible cross section
Use a screened circuit Baumüller-line, optical shield cove
rage > 85%. Do not use single conductors.
For UL conform machines/installations you must use
UL certified circuit cables.
2)
Only for Baumüller cables with this maximum length and by usage of a Baumüller mains filter you can assume, that the limit values of
the EMC product standard EN 61800-3 are complied with.
3)
In case you use parallel-installed motor cables, the maximum length is to be reduced by the factor 1/n.
4)
Connection lugs (current bars). Position see ZFigure 87– on page 186
Screw maximum two cable lugs to the current bar - one on the front side, one on the reverse
side of the bar.