Error handling
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07 Baumüller Nürnberg GmbH
250
of 358
9.4
9.4.2.2 Sub-error messages (3rd level)
P0233 Error power unit - serial interface
Error power unit 80: Communication error
NOTE!
3rd level errors are only displayed in ProDrive separated by a decimal point from the
corresponding 2nd level error (see ZFigure 103– on page 240), exception error pow-
er supply monitor P036 (see ZSeite 253–).
e.g.:
Motor error 102: Group error
Find notch position error 102.64: Drive moved more than 4 times delta angle.
(3rd level)
Error code Meaning Troubleshooting
6 Data overflow Error indicates high EMC problems; please reduce these.
Contact Baumüller Nürnberg GmbH
7 Bit frame error
8 Invalid command state Contact Baumüller Nürnberg GmbH
9 Parity error Restart b maXX 4000
10 Checksum error Error indicates high EMC problems; please reduce these.
Contact Baumüller Nürnberg GmbH
11 Unknown error code
12 Data number error
13 Invalid argument
14 Data field is write protected
15 Invalid access code
16 Data field is not changeable in its size
17 Word address outside of data field
18 Data field is nonexistent
36 Wrong data checksum
37 No response
66 Invalid response Restart b maXX 4000