3.4.1.2 Electrical data BM442X universal units
BM4422 BM4423 BM4424
Rated input power
1)
5.6 kVA 8.6 kVA 11.8 kVA
Rated input current
1)
(I
eff
) 8.1 A 12.4 A 17.0 A
Total harmonic distortion input current (THD)
1)
107 % 109 % 109 %
Current input, max. (I
eff
) 15.1 A 23.2 A 31.8 A
Rated DC link voltage
1)
(U
DC
) 540 V
DC
DC link capacity (internal) 470 F 705 F
DC link discharging time (internal DC link capacity) 340 s
510 s
DC link capacity (external), permitted see ZF
igure 34on page 69
Period between two power up processes
9)
at least 60 s
Output voltage
1)3)
(U
AC
) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
11)
0 Hz to 450 Hz
Rated output current
1)5)6)7)
(I
AC
) at 4 kHz
4)
7.5 A 11.0 A 15.0 A
Rated output current
1)5)6)7)
(I
AC
) at 8 kHz
4)
6.0 A 8.8 A 12.0 A
Output peak current
1)5)6)8)
(I
AC
) at 4 kHz
4)
15.0 A 22.0 A 30.0 A
Output peak current
1)5)6)8)
(I
AC
) at 8 kHz
4)
12.0 A 17.6 A 24.0 A
Max. peak current period
8)
60 s
Power input DC link terminals max. 5.0 kW
Brake resistor current, permitted (Î) max.
9.0 A
max.
13
.0 A
max.
18.0 A
Brake resistor external 86
60 44
Brake resistor threshold (Û) 780 V
Brake resistor peak power 7 kW 10 kW 14 kW
Permitted continuous power
brake resistor external
3.4 kW 5 kW 6.8 kW
Power loss referring to power input 102 W 150 W 204 W
Power input referring to contr
ol voltage max. 63 W
Current of the integrated brake control max. 0.5 A