Monitoring functions
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07 Baumüller Nürnberg GmbH
230
of 358
9.2
9.2 Monitoring functions
A survey of the most important monitoring functions and the generated warning/error
messages you will find in the following table. How to identify the error is explained in
ZFault detection– from page 234.
Monitoring function Warning/error
Warning
Error
Threshold adjustable
Reaction adjustable
Reaction
Adjusting of
limit in parameters
Activation by
parameter
Power supply voltage
6)
Power supply undervoltage X X - - IS - -
Power supply overvoltage X X - - IS - -
Phase monitoring
6)
Phase failure X X - - IS - -
Power failure X X X - IS
2)
P0486 P0486
Ground fault
1)
Fault current to ground - X - - IS - -
Overcurrent Overcurrent motor - X - - IS - -
DC link DC link overvoltage - X - - IS - -
DC link undervoltage relative X - - - - - -
Overload monitoring Peak current
not possible at the moment
X - - - - - -
Temperature heat sink Temperature > threshold 1 X - X - - P0018 -
Temperature > shutdown threshold - X - - IS P0019 -
Temperature internal
space
Temperature > threshold 1 X - X - - P0016 -
Temperature > shutdown threshold - X - - IS P0017 -
Temperature motor I
2
t-threshold exceeded - X - - IS P0073 P0093
Threshold 1 exceeded
3)
X - X - - P0088 P0093
Threshold 2 exceeded
3)
X - X - - P0089 P0093
Short circuit sensor or temp. < -30 °C
3)
- X - - - - P0093
Sensor not connected or temp. > 250 °C
3)
- X - - - - P0093
Maximum temperature exceeded
3)
- X X - IS P0090 P0093
1)
Not available at BM441X and BM442X
2)
Pulse inhibit is generated after adjustable time period
3)
Only when using the KTY sensor
4)
Adjustable with P0299
5)
Adjustable with P0298
6)
Not available at power modules
IS: Pulse inhibit
SH: Quick stop
X: implemented
-: not possible