D9412GV4/D7412GV4/D7212GV4 Introduction | en 11
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
P## Invisible Point = Yes (Keypads do not display alarm activity from this point.)
When using Modem IIIa2 communication type, the unique point text should be set to “Hold-
Up”, or equivalent language per the AHJ.
When using ContactID communication type, because the ContactID system doesn’t provide
custom text, the hold-up point should be associated as a “hold-up” point at the receiving
station. Set Area # Delay Restorals as follows:
Area # Delay Restorals = No (Restoral report is sent when point restores.)
2.4 Guide to Programming Descriptions
Full configuration of the control panel is only achieved through use of the Remote
Programming Software (RPS). A limited set of Tools are available via the keypad to modify
some of the more commonly changed parameters.
This guide is set up in a specific order. Related program entries are grouped together in
modules as they appear in RPS.
This guide shows the programming options for each programming prompt. Each option is
listed with:
The Program Item Prompt. Each prompt is shown as it appears in RPS. Refer to the RPS
Installation Guide (P/N: 4998141259).
Program Entry Default Setting. Because defaults are set for the typical installation,
programming each prompt might not be necessary. Review the default entries in the
program record sheet shipped with the control panel to determine which prompts must
be programmed.
Program Entry Selections. Only the selections listed can be used for a particular program
item.
Program Entry Description. Describes the various entry selections. Read the descriptions
carefully to avoid improperly programmed equipment.
2.5 Guide to Keypad Tools
GV4 now offers a series of tools for configuration and diagnostics through the use of the
keypad with the Service Passcode only. The five configuration tools are:
Programming. For a list of program items you can set using keypad Programming, refer to
Section 2.5.1 Keypad Programming Menu, page 12. To access the Programming menu, the
Keypad Programming option must be set to P (refer to Section 3.12.5 Configuration
Authority, page 101), and all control panel areas must be disarmed.
Service Bypass. For instructions to bypass a point using the keypad’s Service Bypass
menu, refer to Section 2.5.2 Service Bypass Menu, page 14.
RF Points. For a list of program items you can set using the keypad’s RF Points menu,
refer to Section 2.5.3 RF Points Menu, page 14.
RF Repeaters. For a list of program items you can set using the keypad’s RF Repeaters
menu, refer to Section 2.5.4 RF Repeaters Menu, page 15.
RF Diagnostics. For a list of diagnostic items you can perform using the keypad’s RF
Diagnostics menu, refer to Section 2.5.5 RF Diagnostics Menu, page 15.
IP Diagnostics. For a list of diagnostic items you can perform using the keypad’s IP
Diagnostics menu, refer to Section 8.3.1 IP Diagnostics Keypad Menu (B420), page 189.