124 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
Activates when any Non-fire point in the control panel is in a trouble condition. This relay
provides a steady output until the user at the keypad acknowledges the trouble.
Summary Supervisory Burg
Activates when any Non-fire Supervisory point in the control panel is in a supervisory
condition, or if a Supervisory Burg point is missing. This relay provides a steady output until
the user at the keypad acknowledges the condition.
3.14.3 Relay/Output Configuration
Relay/Output Destination
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: On-Board (For Relays A, B, C)
Zonex (For all other relays)
Selection: On-Board, Zonex, Octo-output
On-Board Reserved for on-board outputs A, B and C.
Zonex Output is located on a Zonex relay module on Zonex 1 or Zonex 2.
Octo-output Output is located on a relay module on the SDI2 bus.