D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 23
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Two Phone Lines
Expand Test Report
Use this program item to add system event information to scheduled Test Reports. Refer to
Section 6 Schedules (Skeds), page 154.
3.3 Routing
Use routing to select full or partial groups of events to report to up to eight different
destinations (four over phone, four over network). Routing includes choosing the most
important destination (route number), reporting the events to a single or multiple destination,
and selecting a backup destination if the events fail.
Event routing can be sent over one of the following:
– Standard telephone lines
– Local-area network (LAN)
– Wide-area network (WAN)
– General Packet Radio System (GPRS)
Sending events over a LAN or WAN requires a network interface module (NIM), such as the
DX4020 or B420. Sending events over GPRS requires a special (ITS-DX4020-G).
Default: No
Selection: Yes or No
Yes The D928 Dual Phone Line Module is installed. The LEDs on the D928
light to indicate primary or secondary line trouble and COMM FAIL.
No D928 Dual Phone Line Module is not installed.
NOTICE!
When using two telephone lines, set this parameter to Yes to meet UL 864 requirements
(D9412GV4 and D7412GV4).
NOTICE!
Program Phone Supervision Time when using two phone lines.
NOTICE!
The D7212GV4 does not support the use of the D928 Dual Phone Line Switcher. Leave this
prompt set to its default value.
Default: No
Selection: Yes or No
Yes Off-normal events listed in Routing Group Test Reports are reported to
the central station.
No Off-normal conditions for the events listed in the Routing Group Test
Reports at test time are not reported.
NOTICE!
This parameter relates to Sked Function Code 9 (Test Report) because it allows a Sked to
send Expanded Test Report information. Expand Test Report does not affect Sked Function
Codes 28 (Expanded Off-Normal Test Report) and 29 (Non-Expanded Off-Normal Test
Report).