10 en | Introduction D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
The following programmable parameters are recommended by Bosch when installing a
commercial fire alarm system. Always check with your local Authority Having Jurisdiction.
Table 2.2 UL 864 Programming Requirements
2.3 Guide to UL 636 Programming Requirements for D9412GV4/
D7412GV4/D7212GV4 Control Panels
When using a D9412GV4/D7412GV4/D7212GV4 control panel for hold-up operation, a hold-up
point should have the following setting applied to it:
– P## Type = 0 (Point is constantly armed regardless of the status of the system.)
Path 1 Retry Count Yes 0 to 255 Program as
necessary
45
For Ground Fault
Enable Switch
(Refer to the
D9412GV4/
D7412GV4/
D7212GV4 Operation
and Installation Guide
(P/N: F01U201527)
Yes Closed = Enabled
Open = Disabled
Closed N/A
* Set the Path 1 Poll Rate to 65535 for 24 hr.
Prompt Possible Settings Recommendations
Phone Line Fail Report Yes / No Yes
Phone Line Restoral Report Yes / No Yes
Fire Walk Start Report Yes / No Yes
Fire Walk End Report Yes / No Yes
Cancel Report Yes / No Yes
CC# Scope Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Do not program No
Keypad
CC# Enhanced CommandCenter Yes / No Set to Yes, if
applicable
CC# Menu Key Lock Yes / No If using D1256RB, set
to No
Reset Sensors Disable/Enable/Passcode Protect Enable
Fire Test Disable / Enable / Passcode
Protect
Enable
L## Reset Sensors Disable / Enable If Reset Sensor is set
to Passcode Protect,
set this to Enable
L## Fire Test Disable / Enable If Fire Test is set to
Passcode Protect,
set this to Enable
U### User Group 0 to 8 Program as 0
P## Ring Until Restored Yes / No May be required for
Waterflow, otherwise
No
P## Cross Point Yes / No Set to No for Fire
devices.
D# Fire Unlock Yes / No No
Product Feature/
Option
Permitted in
UL 864? (Y/N)
Possible
Settings
Settings Permitted
in UL 864
Refer to Page: