46 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
computer on which RPS is installed needs a network card. See your information systems
administrator for network requirements.
This section allows you to:
– Provide for local programming by a DX4010V2 Serial Interface Module.
– Provide remote programming by a Conettix DX4020 Network Interface Module, an
ITSDX4020-G, or a B420-G.
– Provide enhanced route paths for event reporting through a network using a Conettix
DX4020 Network Interface Module, an ITSDX4020-G, or a B420-G.
Although not listed in this section, RPS checks for the RPS passcode (refer to Section 3.8 RPS
Parameters, page 54), Datalock Code, and control panel type to determine if this RPS session
should continue.
3.5.1 Configuration for RPS Over Network
COMMAND 43 (Remote Programming) can establish control panel initiated communication
with RPS over the phone or over the network. Figure 3.2, Page 47 and Figure 3.3, Page 48
show the structure of COMMAND 43.
Answer RPS Over Network
This prompt determines if the control panel automatically answers RPS initiated sessions
through a network interface module on the SDI bus.
This prompt can be momentarily disabled by selecting ALLOW ANSWER through COMMAND
43 (Remote Programming) menu (refer to Figure 3.2, Page 47 and Figure 3.3, Page 48).
RPS Address Verification
When enabled, this feature will verify that the Remote Programming Software connecting to
the control panel is coming from a known IP address.
Default Yes
Selection: Yes or No
Yes Enable automatic answer of RPS initiated sessions over the network.
No Do not automatically answer RPS initiated sessions over the network.
NOTICE!
If the Reset switch (labeled S1) label is in the locked position, network RPS programming is
allowed even if this prompt is set to No.
Default No
Selection: Yes or No
Yes Verifies that the incoming RPS network address matches the address
entered in RPS Network Address.
No Do not verify the RPS network address. Allow RPS to connect to the
control panel from any network source .
NOTICE!
If the Reset switch (labeled S1) label is in the locked position, network RPS programming is
allowed even if this prompt is set to No.