50 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
3.6 Power Supervision
AC Fail Time
Program the amount of time that AC power must be off before the control panel responds to
the AC failure. The response to restoral of AC power is delayed for the same amount of time.
AC power is continuously monitored by the control panel, any installed SDI2 bus Power
Supply modules and any installed RF Repeaters. The response to this prompt is the actuation
of the relay programmed in the Panel-Wide Relays prompt AC Failure (refer to
Section 3.14.2 Panel-Wide Relays, page 121) and the AC Fail report enabled by the AC Fail/
Restoral Report prompt. Local annunciation of an AC failure is controlled by the AC Fail
Display prompt.
Resend AC Fail
This prompt controls the repeated transmission of the AC Failure report to the central station
while the fault persists. AC Fail/Restoral Report must be set to Yes, and AC Tag Along must
be set to No for this feature to work. This prompt applies to AC failure events generated by
the control panel, any installed SDI2 bus power supply modules and any installed RF
Repeaters.
AC Fail Display
Default: 1:00
Selection: 0:01 to 90:00 (minutes:seconds)
NOTICE!
UL 864 requirements, Section 50.2.1.b states: “A trouble signal shall be transmitted for
remote station, central station, and proprietary-type protected premises units after a delay of
between 60 and 180 min.
Exception: Products are not prohibited from providing capability of selecting that the primary
power failure trouble signal transmission be delayed other time periods, including no delay,
provided the 60 – 180 min delay is also included.”
To meet UL 864 requirements (D9412GV4 and D7412GV4), program AC Fail Time with 1:00.
Always check with the Authority Having Jurisdiction for local requirements.
Default: No Responses
Selection: No Responses, 6 hrs, 12 hrs
No Response Only send the AC Fail report upon failure.
6 hr Send AC Fail report upon failure and every 6 hours after this while the
failure persists.
12 hr Send AC Fail report upon failure and every 12 hours after this while the
failure persists.
NOTICE!
For the following items to be true, AC Fail/Restoral Report must be programmed as Yes and
AC Tag Along must be programmed as No.
NOTICE!
To eliminate AC Reporting, AC Tag Along and AC Fail/Restoral Report must be programmed
as No.
Default: 60 sec
Selection: 10 to 300 sec (in 5-sec increments)