D9412GV4/D7412GV4/D7212GV4 SDI2 Modules | en 179
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
8 SDI2 Modules
This section discusses programming for the modules that connect to the GV4 Series Control
Panel using the SDI2 bus.
Many devices on the SDI2 bus have a tamper input that you can optionally use to monitor the
device’s enclosure cover or other tamper switch. This prompt has the same options and
purpose for all indicated SDI2 devices.
Enclosure Tamper
8.1 B208 Octo-input Module
The B208 Octo-input module is a device that attaches to the SDI2 bus of the GV4 Series
Control Panel. It provides 8 independently monitored control loops.
Table 8.1 B208 Module Capacities Per Control Panel
RPS supports the configuration of the enclosure tamper on each of the Octo-input modules.
Refer to Section Enclosure Tamper, page 179.
8.2 B308 Octo-output Module
The B308 Octo-output is a device that attaches to the SDI2 bus of the GV4 Series Control
Panel. It provides 8 independently controlled outputs similar in function to those provided by
the Zonex output modules.
Table 8.2 B308 Module Capacities Per Control Panel
RPS supports the configuration of the enclosure tamper on each of the Octo-output modules.
Refer to Section Enclosure Tamper, page 179.
8.3 B420 Ethernet Communication Module
The B420 Ethernet Communication Module is used to connect to the control panel over an
Ethernet network. Typical uses include PC front-end (automation) software packages,
network RPS connection for off-site programming, diagnostic troubleshooting, D6600
NetCom Central Station Receiver (CSR) reporting, and history retrieval. Module bus
supervision is enforced when the SDI2 communication module is used in a central station
reporting route.
Table 8.3 B420 Module Capacities Per Control Panel
Default:No
Selection: Yes or No
Yes The control panel will monitor the tamper status of an SDI2 device and
report its state changes accordingly.
No The control panel will ignore any tamper state changes being sent by an
SDI2 device to the panel.
D9412GV4 D7412GV4 D7212GV4
24 7* 3*
* For the D7412GV4, only 5 inputs are available on the Octo-input at address 7 and for the D7212GV4, only 2
inputs are available on the Octo-input at address 3.
D9412GV4 D7412GV4 D7212GV4
12 6* 2*
* For the D7412GV4, only 4 relays are available on the Octo-output at address 6 and for the D7212GV4 only 4
relays are available on the Octo-output at address 2.
D9412GV4 D7412GV4 D7212GV4
222