178 en | AUXPARM D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
Remote Warning must be set to Yes.
Crystal Time Adjust
When set to Yes, the control panel switches its clock time control from the traditional AC
frequency to the on-board crystal frequency.
Perimeter Relay
When set to Yes, the A# Fail to Close relay becomes an area-wide perimeter armed relay. This
relay is activated when all areas assigned to the same relay have perimeter points that are
armed.
Early Armed Relay
When this prompt is set to Yes, the Area Armed or Perimeter Armed Relay activates at the
beginning of the exit delay time.
Daylight Saving Time
Default No
Selection: Yes or No
Yes Set the clock time control on the control panel to the on-board crystal
frequency.
No Do not set the clock time control on the control panel to the on-board
crystal frequency.
Default No
Selection: Yes or No
Yes Change the function of the area-wide fail-to-close relays to follow the
perimeter armed states of their areas.
No The area-wide fail-to-close relay operates normally.
Default No
Selection: Yes or No
Yes Change activation of Area Armed or Perimeter Armed Relay to the
beginning of the exit delay time.
No Maintain the activation of Area Armed or Perimeter Armed Relay at the
end of the exit delay time.
Default US Calendar
Selection: Disabled or US Calendar
Disabled The control panel clock is not adjusted for daylight saving time.
US Calendar The control panel clock is adjusted to the US start/end dates for
daylight saving.