D9412GV4/D7412GV4/D7212GV4 Points | en 149
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Table 5.2 P## Relay Codes
P### Point Text
Enter alphabetic characters (A to Z) in capital letters.
Enter up to sixteen characters of text to describe the point. This point text is shown at
keypads, if the point is programmed as visible, and sent to the D6500 or D6600 when
transmitting in Modem IIIa
2
format (if it is a reporting point).
Include the point number in custom point text. This helps the user when viewing events,
creating bypasses, and so on. It can also simplify troubleshooting.
P### RFID
A point RFID can be Auto-Learned through the SDI2 bus RF receiver, or it can be entered here.
Auto-Learned RFIDs can be edited for point replacement, or can be set to 0 to disable a RF
point. A RFID (Radio Frequency device IDentification number) is a unique number assigned to
a wireless device at the factory. It provides a unique way for the Wireless Receiver and
Wireless Repeaters to identify what device is transmitting.
5.4 Cross Point Parameters
This section discusses the requirements necessary to program Cross Point functions.
Faults Relay
Relay Code D8129 on Zonex Bus 2
for D9412GV4*
D8129 on Zonex Bus 2
for D9412GV4*
D8129 on Zonex Bus 1
for D7412GV4*
173 9 9
2741010
3751111
4761212
5771313
6781414
7791515
8801616
* Address setting = 1 (on), 2 (off), 3 (on), 4 (on)
NOTICE!
Do not assign a relay to Invisible points. To avoid activating one of the associated relays,
program this prompt as 0.
NOTICE!
Two relays can activate when this point enters into alarm if the P## Relay Response Type for
this point is programmed.
Use these codes to activate relays on the D8129 OctoRelay (or C8137 Transmitter Interface).
You can assign the same code to several points providing a summary zone alarm output. When
the point enters into alarm, the relay activates. When the alarm is acknowledged and is no
longer scrolling in the keypad display, the relay resets.
Default: Refer to the program record sheet
Selection: Up to sixteen alphanumeric characters
Default: 0
Selection: 0 to 99999999