D9412GV4/D7412GV4/D7212GV4 AUXPARM | en 175
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Status Rate
This item determines how often the default status information is sent to the serial interface
module (SIM). The status information includes:
The current point status (normal or off-normal),
The control panel’s area status (Master Armed, Master Instant Armed, Perimeter Delay
Armed, Perimeter Instant Armed, Disarmed, Area Entry Delay, Perimeter Entry Delay, Area
Exit Delay, and Perimeter Exit Delay)
The control panel status (AC Fail, Battery Missing, AC Restore, Battery Low, and so on)
Relay status (relay on or relay off)
Entries are in 100 millisecond increments. If a 5 is entered, the status information is sent
every 500 milliseconds (or 0.5 sec). An entry of 10 equals 1 sec.
7.2 Miscellaneous
Fire Summary Sustain
Use this parameter to set the Summary Fire relay output to continue or to stop after the Fire
Alarm Bell is silenced or times out. Refer to the Summary Fire prompt in Section 3.14.2 Panel-
Wide Relays, page 121.
Fire Supervision Restoral Type
Determines how the control panel sends a Fire Supervision Restoral Event.
NOTICE!
If an SDI2 communication device is allocated for automation communication, then it cannot be
used for central station nor RPS communication.
Default 0
Selection: 0 to 255
0 Status information is sent only when requested.
1 to 255 Status information is sent at the interval programmed.
NOTICE!
If the Status Rate is set to a value less than 10, and 1 to 6 SDI devices are connected to the
system, the fastest the control panel can send the status information is in approximately 1
sec. If more than six SDI devices are connected to the control panel, the fastest the control
panel can send the information is in approximately 1.5 sec to 2 sec. .
Default Yes
Selection: Yes or No
Yes Forces the Summary Fire relay output to remain on after the Alarm
Silence command.
No Allows Summary Fire relay output to be silent when the Fire Alarm Bell
output is silenced and all Fire Points return to normal.
Default 2
Selection: 0, 1, 2
0 The control panel sends a FIRE TROUBLE RESTORE when a Fire
Supervision point restores to normal.
1 The control panel sends a FIRE ALARM RESTORE when a Fire
Supervision point restores to normal.
2 The control panel sends a FIRE SUPERVISION RESTORE when a Fire
Supervision point restores to normal.