D9412GV4/D7412GV4/D7212GV4 Introduction | en 9
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Remote Program Disable /
Enable
-, E, or P Set to P 100
A# Fire Bell Yes 0 to 128, A, B, C0
to 128, A, B, C
Program with a
relay
118
A# Reset Sensors Yes Program with a
relay
119
U### Area # Auth Yes 0 to 8 Program an
Authority Level for
the Fire Area
127
U### Passcode Yes 3-, 4-, 5-, or 6-
digit passcode
Must program at
least one passcode
126
P## Silent Bell No Yes / No Set to No 135
P## Invisible Point No Yes / No Set to No 136
P## Local While
Disarmed
No Yes / No Set to No 139
P## Local While
Armed
No Yes / No Set to No 139
P## Disable
Restorals
No Yes / No Set to No 140
P## Bypassable No Yes / No Set to No 141
P## Swinger Bypass No Yes / No Set to No 142
P## Fire Point Yes Yes / No Set to Yes 143
P## Resettable Yes Yes / No As required 144
Sked## Function
Code
Required 1 to 11, 13 to 28 Sked Function
Code 9
165
Sked## Defer Test No Yes / No Set to No 165
Sked## Hourly
Test(Report?)
No Yes / No Set to No 165
Sked## Time Enter valid
time
00:00 to 23:59 00:00 to 23:59 171
Sked## Date No mm/dd Set to No 171
Sked## Sunday Yes Yes / No Set to Yes 171
Sked## Monday Yes Yes / No Set to Yes 172
Sked## Tuesday Yes Yes / No Set to Yes 172
Sked## Wednesday Yes Yes / No Set to Yes 172
Sked## Thursday Yes Yes / No Set to Yes 172
Sked## Friday Yes Yes / No Set to Yes 172
Sked## Saturday Yes Yes / No Set to Yes 172
Sked## Xept On
Holiday
No Yes / No Set to No 172
For IP
Communications to
a D6600 Receiver
Enhanced Comm Yes Yes / No Set to Yes 40
Path1 IP Add1 (2, 3
or 4)
Yes 000 to 255 Program a valid IP
address
41
Path 1 Poll Rate Yes 0, 5 to 65535
sec*
Program as
necessary
41
Path 1 Ack Wait Yes 0, 5 to 65535
sec*
Program as
necessary
45
Product Feature/
Option
Permitted in
UL 864? (Y/N)
Possible
Settings
Settings Permitted
in UL 864
Refer to Page: