140 en | Points D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
P## Disable Restorals
* Transmission of Restoral Reports continues if the alarm, trouble, or bypass (by Sked, RPS,
or Swinger bypass) condition occurred when the area disarmed, and the point restored.
Use this option to disable any Restoral Reports from this point after it returns to normal from
an alarm or trouble condition.
P## Force Arm Returnable
Use this option to allow points that were force armed out of the area to return back to the
armed state when they become normal again without having to disarm the system.
P## Bypass Returnable
Use this option to return a point that was bypassed, force armed, or swinger bypassed back
into the system when the area to which this point is assigned is disarmed. This option applies
to all point types.
NOTICE!
Local While Armed suppresses all reports from 24-hour points. Do not use P## Type 0 for this
prompt. This setting works only for disarmed points. Type 0 is a 24-hour, always armed point.
Choose any Type other than 0, and use a point response that reports an alarm whether or not
the point is armed. For instance, P## Type 1 and P## Response 9 reports an alarm on a trouble
or a short whether or not the area is disarmed.
Local While Armed affects Keyswitch Points. This prompt suppresses keyswitch (alarms,
troubles, and restorals) and D279 (opening, closing, troubles, and restorals). Do not use this
parameter for controlled points that arm or disarm.
Default: Refer to the program record sheet
Selection: Yes or No
Yes Enable Restoral Reports from this point.
No Disable Restoral Reports from this point.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), set this parameter to No.
Default: Refer to the program record sheet
Selection: Yes or No
Yes This point automatically returns to the system when it restores to
normal.
No This point stays out of the system until the area is disarmed.
NOTICE!
Use on loading dock doors, that must remain open until loading is completed. After the
loading dock door is closed, the point detects any subsequent opening and reports an alarm.
Default: Refer to the program record sheet
Selection: Yes or No
Yes This point automatically returns to the system when the area is
disarmed.
No This point stays out of the system through arming and disarming cycles.
NOTICE!
Set this item to No for Interlock points.