D9412GV4/D7412GV4/D7212GV4 Points | en 139
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Use P## Display as Device to cause the keypad to display CHECK DEVICE when a point is off-
normal or is acknowledged after going into alarm.
P## Local While Disarmed
* Transmission of Restoral Reports continues if the alarm, trouble, or bypass (by Sked, RPS,
or Swinger bypass) condition occurred when the area disarmed, and the point restored.
Use this option to allow a Controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and
Restoral Reports only when the area is armed. This prompt does not affect local annunciation.
P## Local While Armed
* Transmission of Restoral Reports continues if the alarm, trouble, or bypass (by Sked, RPS,
or Swinger bypass) condition occurred when the area disarmed, and the point restored.
Allows a controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and Restoral Reports
only when the area is disarmed. This prompt does not affect local annunciation.
NOTICE!
Use this function for devices with a dry contact output that faults a point when the device is in
a trouble condition.
Default: Refer to the program record sheet
Selection: Yes or No
Yes Suppress Alarm, Trouble and Restoral* Reports from this point while
the area to which it is assigned is disarmed.
No Send event reports occurring from this point while the area is
disarmed.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), set this parameter to No.
NOTICE!
Local While Disarmed suppresses all reports from 24-hour points. Do not use P## Type 0 for
this prompt. Remember that this option works only for Disarmed points, and a Type 0 is a 24-
hour Always Armed point. Instead, choose any type other than 0, and use a point response
that reports an alarm, whether or not the point is armed. For instance, P## Type 1 and P##
Response 9 reports an alarm on an open or a short (I) whether the area is armed or not.
Local While Disarmed affects Keyswitch points. This prompt suppresses keyswitch (troubles
and restorals) and D279 (alarms, troubles, and restorals). Do not use this parameter for these
applications.
Default: Refer to the program record sheet
Selection: Yes or No
Yes Suppress Alarm, Trouble and Restoral* Reports from this point while
the area to which it is assigned is armed.
No Report events occurring from this point while the area is armed.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), set this parameter to No.