122 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
Battery Trouble
Activates when battery voltage falls below 85% of capacity (12.1 VDC) for a fully charged
(13.8 VDC) battery, or when the battery is in a missing condition. This relay automatically
resets when battery power restores.
Phone Fail
Activates when a telephone line failure occurs. A time must be entered in Ph Supv Time (refer
to Section 3.2 Phone Parameters, page 19) for this relay to activate. This relay resets
automatically when restoral of the phone line(s) occurs.
Comm Fail
Activates when a control panel cannot communicate a report after making ten attempts to
each routing destination. At the same time, COMM FAIL RG displays at the keypad. This relay
automatically resets when a report is sent successfully.
Log % Full
This parameter determines how full the memory log should be before initiating a call to RPS at
the central station. This allows the memory log to be copied by RPS before messges can be
overwritten. An entry of 0 (zero) disables the LOG THRESHOLD and LOG OVERFLOW events.
These events are not put in the log nor reported to the D6500/D6600 or to the local
printer.The control panel continues to log events after the LOG THRESHOLD report is sent.
NOTICE!
Use this relay to create audible annunciation. Enable the keypad’s trouble sounders for all
applications except commercial fire systems.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
NOTICE!
Use this relay to create audible annunciation. Enable the keypad’s trouble sounders for all
applications except commercial fire systems.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
NOTICE!
Use this relay to report primary digital report failure to an alternate communication device.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4