D9412GV4/D7412GV4/D7212GV4 Points | en 137
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Use this option to determine whether the point appears in the keypad display upon an alarm
condition. For LED keypads, the LED does not illuminate upon an alarm condition. Point text
appears and annunciation is made for Invisible points programmed for a trouble condition in
point response.
P## Buzz On Fault
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to No.
NOTICE!
To prevent the keypad alarm tone and the A# Burg Alarm bell from sounding, program P##
Silent Bell as Yes.
NOTICE!
If a user enters a valid passcode while a bell is ringing for an invisible alarm, the keypad shows
ALARM SILENCED.
Default: Refer to the program record sheet
Selection: 0 to 3
Selection: Operation for Controlled Points (Point
Types 1, 2, and 3)
Operation for 24-hour, Fire and Aux AC
Supervision Points (Point Types 0 and
11)
0 The point buzzes at the keypad only if it
enters into the trouble condition
indicated in the P## Point Response.
Same as operation for controlled
points
1 The point generates a Buzz Until Restore
at the keypad for any fault condition
while the point is disarmed. The buzz
continues until the point restores and
the user acknowledges the condition
using a passcode or COMMAND 4. The
point must be normal before the user
can silence the buzz.
The point generates a Buzz Until
Restore at the keypad for any fault
condition regardless of the armed
state. The buzz continues until the
point restores and the user
acknowledges the condition using a
passcode or COMMAND 4. The point
must be normal before the user can
silence the buzz.
2 The point buzzes at the keypad for any
fault condition when the point is
disarmed. The user can silence the buzz
before the point returns to normal.
The point buzzes at the keypad for any
fault condition regardless of the
armed state. The point does not need
to be normal before the user can
silence the buzz.
3 The point buzzes at the keypad for any
fault condition when the area is
disarmed. The user cannot silence this
buzz, but it silences automatically when
the point is restored. If the fault
condition results in a trouble response,
the keypad continues to buzz even after
the user acknowledges the condition if
the fault is still present.
The point buzzes at the keypad for any
fault condition regardless of the
armed state. The user cannot silence
this buzz, but it silences automatically
when the point is restored. If the fault
condition results in a trouble response,
the keypad continues to buzz even
after the user acknowledges the
condition if the fault is still present.