D9412GV4/D7412GV4/D7212GV4 ACCESS CONTROL (D9412GV4/D7412GV4) | en 201
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
D# Access Granted?
This program item determines if Access Granted and Door Request Events are sent to the
control panel for processing memory, printing, and remote reporting.
D# No Entry?
This program item determines if No Entry Events are sent to the control panel for processing
memory, printing, and remote reporting.
D# Enter Request?
This program item determines if RTE Events are sent to the control panel for processing
memory, printing, and remote reporting.
Default: Yes
Selection: Yes or No
Yes Access Events from this door controller are sent to the control panel for
processing.
No Access Events from this door controller are not sent to the control
panel for processing.
NOTICE!
A successful Access Event can be started by a:
–Valid user ID
– Valid door state changed at the keypad
– Scheduled or armed state change that holds a door open
–RTE or REX
Default: Yes
Selection: Yes or No
Yes Access Denied Events from this door controller are sent to the control
panel for processing.
No Access Denied Events from this door controller are not sent to the
control panel for processing.
NOTICE!
No Entry Event can be caused by:
– Invalid or unknown user ID, interlock or secured door, or incorrect authority level
– RTE or REX at an interlocked door
– RTE or REX at a door in the secured mode
Default: No
Selection: Yes or No
Yes A Door RTE Event from this door controller is sent to the control panel
for processing.
No A Door RTE Event from this door controller is not sent to the control
panel for processing.
NOTICE!
RTE Events require D# Access Granted to be programmed as Yes.