DS7200V2-EXP | Installation Guide | 4. Reference Materials
EN | 113
Table 40: Control Panel Events and Reporting Formats (continued)
Event
Event as shown
in Control Panel
Log
SIA Report
Contact ID
Report
Event Description
Zone Types
Linked to
Event
RPS
Event
Group
Status
Report
74* Duress HA Hold Up
Alarm
121 Duress User entered Duress PIN or
pressed Panic key sequence or
[Q] button** on RF Keyfob. The
Duress report is sent in addition
to any other report that the
user’s action would generate.
1
75 Fire,Alarm FA Fire Alarm 110 Fire Alarm event on fire zone type. 1- Fire
2- Fire with
Alarm
Verification
2
76 Fire,Cross FM Fire Alarm
Cross Zone
110 Fire Verified alarm event on fire zone
type with Cross Zone Option.
See “Zone Response Options” in
the DS7200V2 Expert
Programming Guide (P/N:
4998153891).
1- Fire
2
77
Fire,Un-verified
FG Unverified
Event-Fire
378 Cross-
zone Trouble
Unverified alarm event on fire
zone type with Cross Zone
Option. Or unverified event on
Fire Verify zone type.
1- Fire
2- Fire with
Alarm
Verification
5
78 Fire, Missing FY Missing Fire
Trouble
373 Fire
Trouble
Fire zone type assigned to zone
expander (wired or RF) not
responding to panel’s status poll.
1- Fire
2- Fire with
Alarm
Verification
5
79 Fire,Alrm,Rstl FH Fire Alarm
Restore
110 Fire Restoral from alarm, Fire zone
types.
1- Fire
2- Fire with
Alarm
Verification
7
80 Fire,Trouble FT Fire Trouble 373 Fire
Trouble
Fault (Trouble) condition on Fire
zone types.
1- Fire
2- Fire with
Alarm
Verification
5
81 Fire,Trbl,Rstl FJ Fire Trouble
Restore
373 Fire
Trouble
Restoral from Trouble, Fire zone
types.
1- Fire
2- Fire with
Alarm
Verification
7
82 Instl Mode,Start LB Local
Program
466 Service
On Premises
Installer PIN entered. Installer
mode accessed.
11 R
83 Instl Mode,End LX Local
Programming
Ended
466 Service
Off Premises
Installer mode exited. 11 R
84 Log Overflow JO Log Overflow 624 Event Log
Overflow
Panel log overflow condition.
Oldest events being overwritten.
12 R
85 Log Threshold JL Log
Threshold
623 Event Log Panel log reached threshold. See
“Log Supervision Configuration
in the DS7200V2 Expert
Programming Guide.
12 R
86 AltCom Low Signl XL Low Received
Signal Strength
350
Communicatio
n Trouble
Low Signal Strength detected on
Alternate Communication device.
12 R S
* This event reports a user number + 200 when sent using SIA and Contact reporting formats.
** See the DS7200V2 Expert Programming Guide (P/N: 4998153891) for information on [Q] button programming.