Page 6845349D © 2002 Radionics
D6412/D4412 Installation Guide
D6412/D4412
Enclosures
Radionics offers three optional enclosures for the control/communicator.
• The D8103 enclosure is suitable for residential fire and/or burglary installations and commercial burglary
applications that do not require attack resistance or approval by Factory Mutual or NYC-MEA. (See the
Appendix B: System Chart for acceptable applications.)
• The D8108A is attack resistant. It is intended primarily for UL commercial burglar alarm and mercantile safe
and vault applications requiring a local bell. You can use the D8108A in any burglar or fire alarm application
where the 5591 or D8109 enclosure is suitable. UL lists the D8108A for all commercial fire alarm applications.
The D8108A is approved by Factory Mutual, California State Fire Marshal, and the New York City Materials
and Equipment Acceptance System.
• The D8109 is normally used for commercial fire alarm applications. UL lists the D8109 for all commercial fire
alarm applications. The D8109 is approved by the California State Fire Marshal, NYC-MEA and FM.
IMPORTANT
All references to NFPA and related requirements are based upon compliance with the 1993 edition of
NFPA 72, National Fire Alarm Code. Since installation specifications are nearly always based upon a
specific edition of a standard which has been legally adopted by the Authority Having Jurisdiction (AHJ),
earlier editions of NFPA standards will generally apply. Consult with the appropriate AHJ for
confirmation.
System Chart
Household Burglary
(Grade A)
Household Fire
Household Fire/Burglary
Combined
Central Station Burglary
(Grade C)
Police Connected
Burglary
Local Burglary
Mercantile (4 hrs)
Commercial
Mercantile (72 hrs)
Bank Safe/Vault Alarm
Proprietary Burglary
NFPA Standard 72 72
Min. Hrs of Standby
Battery
4 24 hrs +
4 min
24 hrs +
4 min
4 4 4 4 72 4
Entry/Exit Time (sec) 45/60 45/60 45/60
Bell Time (minutes) 4 4 4 15 15 15 15 15 15
D2203 Enclosure Included w/ panel No No No No No No
D8103 Enclosure* Optional No No No No No
D8108A Enclosure Optional Req Req Req Req Req
D8109 Enclosure Optional
Choose
One
No No No No No
D126 Battery (7 Ah) Req Req Req Req Req Req Req No Req
D1218 Battery (18 Ah) Opt Opt Opt Opt Opt Opt Opt Req Opt
D127 Reversing Relay Opt Opt Opt Opt Opt Opt Opt Opt Opt
D132A Smoke
Detector Reversing
Relay Module
Required if D192C is not used. Use the D132A with compatible smoke detectors only.
D164 Telephone Cord Required to connect panel to RJ131X Telco Block.
D192C NAC
Supervision Module
Required if D132A and compatible smoke detectors
are not used.
D621, D623, D625
Command Center
1+ 1+ 1+ 1+ 1+ 1+ 1+ 1+ 1+
D262 Smoke Detector
Head/D621 Base
1• 1•
D282THS Smoke
Detector w/ Sounder
Use with D132A.
D431, D435, D438,
D440, D442, D448
Indicating Device
1+ 1+ 1+ Opt
♦ ♦ ♦ ♦ ♦
CX4010 Transformer Required for all applications.
D8004 Transformer
Enclosure
Opt Opt Opt Opt Opt Opt
D8122 Derived
Channel STU
Optional. Contact Telco availability of derived channel
service.
D8130 Release
Module
Optional
Appendix A
Key
No Not acceptable for this
application.
Req Required for this
application.
Opt Optional for this
application.
1+ 1 or more required for
this application. Consult
the appropriate standard.
1l At least one detector
required. You can
substitute other 2-wire
detectors listed for use
with the D6412/D4412.
You could use the D262
with the D270 4-wire
base or other
manufacturer's 4-wire
detectors. You must use
a listed power
supervision relay with 4-
wire detectors.
w
UL Listed bell (siren)
housing required for
burglary alarm bell or
siren (Rothenbuhler 5110
Bell).
Empty Cell Not used for this
application.
* Not to exceed these
Entry/Exit Delay limits for
UL installations.
** D101 for this application.