Page 7045349D © 2002 Radionics
D6412/D4412 Installation Guide
D6412/D4412
Appendix A
Current Rating Chart for Standby Battery Calculations
A
AC Power On
Normal Current
B
AC Power Off
Minimum Current
C
In Alarm
Maximum Current
Model Number
Quantity
Used
Each
Unit* Total
Each
Unit Total
Each
Unit Total
D6412/D4412 _______ 85 x 1 = 85 85 x 1 = 85 100 x 1 = 100
Keypads
D621 _______ 35
x Qty
= _____ 35
x Qty
= _____ 115
x Qty
= _____
D623 _______ 100
x Qty
= _____ 100
x Qty
= _____ 100
x Qty
= _____
D625 _______ 270
x Qty
= _____ 270
x Qty
= _____ 270
x Qty
= _____
Accessories
DX2010 _______ 35
x Qty
= _____ 35
x Qty
= _____ 35
x Qty
= _____
DX3010 _______ 10
x Qty
= _____ 10
x Qty
= _____ 10
x Qty
= _____
DX3020 _______ 10
x Qty
= _____ 10
x Qty
= _____ 10
x Qty
= _____
DX4010 _______ 25
x Qty
= _____ 25
x Qty
= _____ 25
x Qty
= _____
RF3224 _______ 30
x Qty
= _____ 30
x Qty
= _____ 30
x Qty
= _____
Sounders connected to PO 2
D118 8
Ω
Speaker*** _______ 0
x Qty
= _____ 0
x Qty
= _____ 330
x Qty
= _____
Ratings of other devices in the system which are not shown above:
__________ _______ ____
x Qty
= _____ ____
x Qty
= _____ ____
x Qty
= _____
__________ _______ ____
x Qty
= _____ ____
x Qty
= _____ ____
x Qty
= _____
__________ _______ ____
x Qty
= _____ ____
x Qty
= _____ ____
x Qty
= _____
__________ _______ ____
x Qty
= _____ ____
x Qty
= _____ ____
x Qty
= _____
__________ _______ ____
x Qty
= _____ ____
x Qty
= _____ ____
x Qty
= _____
Total A
= _____
Total B
= _____
Total C
= _____
* Currents shown in milliamperes (1 ampere = 1000 milliampere)
** If the column C total exceeds 400 mA (600 mA for non UL applications), a D8132 is required to provide an additional
1400 mA. You may also use a UL Listed external power supply for this purpose
*** Not investigated by UL