7–41 62-11785
P00157 CHECK BATTERY CURRENT
ACTIVATION: With all circuits off, current flow of more than +1.5 to -2.0 amps is detected in the 12 VDC
electrical circuits.
NOTE: If this alarm occurs, Pretrip Test #2 will be skipped and Pretrip Test #3 will start.
UNIT CONTROL: Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.
RESET CONDITION: Auto reset if Pretrip is started again, or alarm may be manually reset using the dis-
play mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check DC Current Draw and Sensor
a. Observe current draw reading in unit data. Reading must be between +1.5 to -2.0 Amps.
b. Check power between 2MM-29 and 2MM-23 and between PCM-31 and PCM-30. Verify 5 VDC. If
not, check connectors and wiring between terminals for damage, moisture or corrosion.
c. Check for continuity from 2MM-12 to PCM-29. If good continuity not present, check connectors
and wiring between terminals for damage, moisture or corrosion.
2. Check Individual Circuits - Isolate individual circuits and test amp draw. Must be in range. (Refer to
Section 2.10 for correct electrical values.)
3. Check For Parasitic Loads - Check for electrical loads that are drawing current with all circuits OFF.
Check for non-factory installed devices such as lift gates, inside lights, satellite systems, etc. These
devices must be wired so as to not draw current during Pretrip testing.
P00158 CHECK AMBIENT AIR SENSOR
ACTIVATION: Ambient Air Temperature Sensor (AAT) is not within the range of -53 to +158°F (-47 to +70°C).
UNIT CONTROL: Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.
RESET CONDITION: Auto reset if Pretrip is started again, or alarm may be manually reset using the dis-
play mounted keys or by turning the unit off, then back on again.
CORRECTIVE ACTIONS:
Check sensor operation - Refer to procedure for alarm 00121 CHECK AMBIENT AIR SENSOR.
Alarm condition must be corrected and the alarm cleared to continue.
P00159 CHECK DEFROST TERM 1 SENSOR
ACTIVATION: Defrost Termination Temperature Sensor (1DTT) is not within the range of -53 to +158°F
(-47 to +70°0 C.)
UNIT CONTROL: Pretrip will fail and display “PRETRIP FAIL AND COMPLETED”.
RESET CONDITION: Auto Reset if Pretrip is started again, or alarm may be manually reset via keypad or
by turning the unit off, then back on again.
CORRECTIVE ACTIONS:
Check sensor operation - Refer to procedure for alarm 00124 CHECK DEFROST TERM 1 SENSOR.
Alarm condition must be corrected and the alarm cleared to continue.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier TRANSICOLD VECTOR 8100 and is the answer not in the manual?

Carrier TRANSICOLD VECTOR 8100 Specifications

General IconGeneral
BrandCarrier TRANSICOLD
ModelVECTOR 8100
CategoryRefrigerator
LanguageEnglish

Related product manuals