62-11785 7–90
28002 NO COMM FROM DOOR SWITCH
• ACTIVATION: The door switch configuration is configured as 3rd Party and no communications have
been received for 15 minutes
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Communications have been received from the door switch.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check for proper APX Control System Configuration - Refer to Section 5.2.3 & Table 5–1.
2. Make sure that all third party configurations are correct and software is current.
Check Switch and Wiring - Inspect switch, connector pins & terminals. No physical damage to sen-
sor. No damaged or corrosion in connections.
28003 INVALID DOOR SWITCH
• ACTIVATION: The Door Switch configuration is configured as 3rd Party and data received from the switch
is invalid.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Valid data received from door switch.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check for proper APX Control System Configuration - Refer to Section 5.2.3 & Table 5–1.
2. Make sure that all third party configurations are correct and software is current.
Check Switch and Wiring - Inspect switch, connector pins & terminals. No physical damage to sen-
sor. No damaged or corrosion in connections.
28004 INVALID REMS1
28005 INVALID REMS2
• ACTIVATION: The Remote Switch configuration is configured as 3rd Party and data received from the
switch is invalid.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Valid data received from remote switch.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in Notes Section) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check for proper APX Control System Configuration - Refer to Section 5.2.3 & Table 5–1.
2. Make sure that all third party configurations are correct and software is current.
Check Switch and Wiring - Inspect switch, connector pins & terminals. No physical damage to sen-
sor. No damaged or corrosion in connections.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier TRANSICOLD VECTOR 8100 and is the answer not in the manual?

Carrier TRANSICOLD VECTOR 8100 Specifications

General IconGeneral
BrandCarrier TRANSICOLD
ModelVECTOR 8100
CategoryRefrigerator
LanguageEnglish

Related product manuals