7–83 62-11785
23100 NO COMM FROM MICRO TO OUTPBD1
• ACTIVATION: Main microprocessor cannot communicate internally.
• UNIT CONTROL: Required Shutdown. If alarm remains active for 2 minutes issue a shutdown command
to all modules except the display.
• RESET CONDITION: Auto reset when internal communication is restored, alarm reset or alarm may be
manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in Notes Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
Replace Main Microprocessor - Download data and replace main microprocessor. For complete Main
Microprocessor Module replacement instructions refer to Section 5.5.2.
23101 OUTPUT LOST CONFIGURATION
• ACTIVATION: Output Board reports an invalid configuration.
• UNIT CONTROL: Required Shutdown.
• RESET CONDITION: Auto reset when communication is restored, or alarm may be manually reset by
turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in Notes Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check Wiring - Check logic power connections. Check wiring at 1MM-6 & 1MM-1.
2. Replace Main Microprocessor - Download data and replace main microprocessor. For complete Main
Microprocessor Module replacement instructions refer to Section 5.5.2.