EasyManuals Logo

CG emotron TSA Series User Manual

CG emotron TSA Series
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
100 Functionality CG Drives & Automation, 01-5980-01r2
Minimum Pre-Alarm [413]
These menus contain the settings for the load monitor
minimum pre-alarm.
Minimum Pre-Alarm Action [4131]
Setting of the alarm behaviour when a “Minimum Pre-
Alarm” has been detected.
Minimum Pre-Alarm Level [4132]
The value of the minimum pre-alarm level is given as a
percentage of the nominal motor power [223]. When the
actual shaft power (shown within brackets in the display) falls
to a value below this level, the “Minimum Pre-Alarm Delay
timer, menu [4133], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Minimum Pre-Alarm Action” in menu
[4131].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an “Autoset”. See
further information in Fig. 40, page 57.
Example:
The “Min Pre-Alarm Level” is set to 40%. This means that
when the shaft power falls to a value below 40% of the
nominal motor power, the alarm delay timer starts counting
down.
Minimum Pre-Alarm Delay [4133]
When the load level falls below the alarm level for a
continuous period longer than the set “Min Pre-Alarm
Delay” time, the selected “Minimum Pre-Alarm Action” in
menu [4131] is activated..
Minimum Alarm [414]
These menus contain the settings for the load monitor
minimum alarm.
Minimum Alarm Action [4141]
Setting of the alarm behaviour when a “Minimum Alarm
has been detected.
Minimum Alarm Level [4142]
The value of the minimum alarm level is given as a
percentage of the nominal motor power [223]. When the
actual shaft power (shown within brackets in the display) falls
to a value below this level, the “Minimum Alarm Delay
timer, menu [4143], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Minimum Alarm Action” in menu [4141].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an Autoset”. See
further information in Fig. 40, page 57.
Default: No Action
No Action 0
For a definition, see Table 23, page 55.
Hard Trip 1
Soft Trip 3
Warning 4
Default: 92%
Range: 0 - 200% of nominal motor power [223]
4131 MinPreAlAct
Stp No Action
4132 MinPreAlLev
Run (P
shaft
%) 92%
Default: 0.5 s
Range: 0.1–90 s
Default: No Action
No Action 0
For a definition, see Table 23, page 55.
Hard Trip 1
Soft Trip 3
Warning 4
Default: 84%
Range: 0 - 200% of nominal motor power [223]
4133 MinPreAlDel
Stp 0.5s
4141 MinAlarmAct
Stp No Action
4142 MinAlarmLev
Run (P
shaft
%) 84%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CG emotron TSA Series and is the answer not in the manual?

CG emotron TSA Series Specifications

General IconGeneral
BrandCG
Modelemotron TSA Series
CategoryController
LanguageEnglish

Related product manuals