CG Drives & Automation 01-5980-01r2 Technical data 159
1) Normal duty: Start current = 3 x I
n_soft
, Start time = 15 s (Size 1) or 30 s (Size 2-4), 10 starts/hour,
Heavy duty: Start current = 5 x I
n_soft
, Start time = 15 s (Size 1) or 30 s (Size 2-4), 10 starts/hour.
2) Fuse data for Semi-conductor fuses, see Table 48.
3) H1=Height of enclosure, H2= Total height.
Table 46 Technical data for Emotron TSA52/69-240 to -450.
Emotron TSA Size 4 model:
TSA52/69-240 TSA52/69-300 TSA52/69-360 TSA52/69-450
Duty
(1)
Normal Heavy Normal Heavy Normal Heavy Normal Heavy
Rated current I
n_soft
[A] 240 144 300 180 360 216 450 270
Motor size P
n_mot
400 V [kW] - TSA52-### 132 75 160 90 200 110 250 132
Motor size P
n_mot
460 V [hp] - TSA52-### 200 100 250 125 300 150 350 200
Motor size P
n_mot
525 V [kW] - TSA52-### 160 90 200 132 250 160 315 180
Motor size P
n_mot
575 V [hp] - TSA69-### 250 150 300 150 350 200 450 250
Motor size P
n_mot
690 V [kW] - TSA69-### 250 132 315 160 355 200 450 250
Recommended load fuses [A]
(2)
315 315 355 355 400 400 500 500
Total power loss for TSA unit at rated motor
power, in bypass mode [W]
55 37 69 43 84 50 109 62
Total average power loss for TSA unit if
10 starts/hour [W]
269 251 350 327 377 346 474 431
Dimensions H1/H2 x W x D [mm (in)]
(3)
373/512 x 254 x 260 (14.9/20.2 x 10 x 10.3)
Mounting position Vertical/Horizontal
Weight [kg (lb)] 23.5 (51.8)
Busbar for cable connection [mm (in)] 40 x 10 (1.6 x 0.39), Ø 13 connection.
Possible to use either Cu or Al cables.
Cooling system Fan
Protection class IP20
UL short circuit rating 30 kA