24 Connections CG Drives & Automation 01-5980-01r2
Example 1: Separate Start- Stop-signals ( 3-
wire connection).
• Closing (pulse) contact between terminal 18 (24 VDC)
and terminal 11(DigIn1) gives Start.
Opening (pulse) contact between terminal 18 (24 VDC)
and terminal 12(DigIn2) gives Stop. To make Emotron
TSA start, terminal 12 (DigIn2) must be connected to
terminal 18 (24VDC).
Fig. 20 Separate Start- Stop-signals ( 3-wire connection) wir-
ing example.
NOTE: This alternative works with the factory default
parameter settings.
NOTE: With this alternative the softstarter will not
restart after a power failure. A new start pulse must be
given.
DigIn 1 DigIn 2 +10 V AnIn GND DigIn 3 DigIn 4 +24 V AnOut +24 V
Relay 1 Relay 2 Relay 3
StopRun FWD
PTC