Common procedures 10-3
6200 Packet-Optical Platform Installation, Commissioning, and Testing Procedures
Release 1.1 009-6200-201 Draft Issue 1
Copyright
©
2014 Ciena
®
Corporation September 2014
Procedure 10-1 (continued)
Inserting the power supply unit-DC PSU/Fan+OAM/ Fan+OAMV2 module
Step Action
2 Determine whether two DC PSUs are working in the system.
3 Insert the power supply-DC PSU/Fan+OAM/Fan+OAMV2 unit.
Note: Fan+OAM or Fan+OAMV2 module is hot swappable. Hot swappable is
the ability to replace a defective component while the system continues to
function normally.
4 Slide in the power supply unit-DC PSU/Fan+OAM/Fan+OAMV2 module
along the guide ways provided on the chassis.
5 Insert the power supply unit-DC PSU/Fan+OAM/Fan+OAMV2 module
securely to the backplane of the 6200 network element.
6 Fasten the module to the chassis using a manual Phillips (PH1) screwdriver.
—end—
If the system has Then
two power supply units in working
condition
power supply units are hot
swappable.
eject the required power supply unit
to be replaced.
Go to step 4.
only one power supply unit in
working condition
power down the distribution frame
and eject the power supply unit, see
Risk of Service disruption.
Go to step 4.
CAUTION
Risk of Service disruption
The power supply unit is not hot swappable. This action
is service disruption.
where engages the
slot 8/slot 9 power supply unit- DC PSU
slot 10 Fan+OAM or Fan+OAMV2
CAUTION
Risk of performance degradation
Failure to fasten the face plate to the sub rack may
result in intermittent failures, because of poor
connectivity.