5. Set the grid standard. From the previous menu press ESC to return
to the System Parameters menu. If the display had been previously
returned to the main menu, follow the steps in (4) to access System
Parameters again. Select System Parameters, press ENT. Scroll
to Grid Connection Rule and press ENT.
Use the arrow buttons to move up/down to the required grid standard.
Press ENT to select the required standard.
INSTRUCTION:
Check with your local utility company before selecting a grid standard.
If the inverter is operating with a wrong grid standard, the utility
company may cancel the interconnection agreement.
Placing the inverter into operation before the overall system complies
with the national rules and safety regulations of the application is not
permitted.