88
Table 4-5 HVRT Parameters (IEEE5147 and Rule21)
HVRT
IEEE1547
Rule21
Parameter name
Description
Setting Range
(Min, Default, Max)
Setting Range
(Min, Default, Max)
HVRTVolt (1,2)
Threshold value of high
voltage ride through (1
st
& 2
nd
point)
{100%, 125%, 135%}
{100%, 125%, 135%}
{100%, 125%, 135%}
{100%, 125%, 135%}
HVRTTime (1,2)
Time of Level high voltage
ride through (1
st
& 2
nd
point)
{0, 0, 655}
{0, 0.8, 655}
{0, 0, 655}
{0, 0.11, 655}
HVRTVolt (3,4)
Threshold value of high
voltage ride through (3
rd
& 4
th
point)
{100%, 124%, 135%}
{100%, 124%, 135%}
{100%, 120%, 135%}
{100%, 120%, 135%}
HVRTTime (3,4)
Time of Level high voltage
ride through (3
rd
& 4
th
point)
{0, 0.8, 655}
{0, 12.5, 655}
{0, 0.11, 655}
{0, 12.5, 655}
HVRTVolt (5,6)
Threshold value of high
voltage ride through (5
th
& 6
th
point)
{100%, 115%, 135%}
{100%, 115%, 135%}
{100%, 110%, 135%}
{100%, 110%, 135%}
HVRTTime (5,6)
Time of Level high voltage
ride through (5
th
& 6
th
point)
{0, 12.5, 655}
{0, 12.5, 655}
{0, 12.5, 655}
{0, 12.5, 655}
HVRTVolt (7,8)
Threshold value of high
voltage ride through (7
th
& 8
th
point)
{100%, 115%, 135%}
{100%, 115%, 135%}
{100%, 110%, 135%}
{100%, 110%, 135%}
HVRTTime (7,8)
Time of Level high voltage
ride through (7
th
& 8
th
point)
{0, 12.5, 655}
{0, 12.5, 655}
{0, 12.5, 655}
{0, 12.5, 655}