125
Table 8-5 LCD Troubleshooting FAULT cont’d
Fault
Fault0130
(Bus over total
voltage)
1. Restart inverter by turning both AC and DC
switches OFF. Wait for 1 minute for all energy to
discharge between OFF and turn both switches ON
2. If inverter cannot clear fault, replace inverter
Fault0150
(Open-loop
self-check failure)
1. Restart inverter by turning both AC and DC
switches OFF. Wait for 1 minute for all energy to
discharge and turn both switches ON
2. If inverter cannot clear fault, replace inverter