User Manual DEV 1951
Copyright DEV Systemtechnik GmbH 2004-2017 123
5.9.4.4.4.4 .surveillance.errorTable.errorEntry.errorDateTime
OID: .1.3.6.1.4.1.21035.41.3.4.1.4.x
Syntax: INTEGER32
Access: read-only
Description: The last occurrence of the event
(Unix time stamp, seconds since 01-Jan-1970 00:00:00 UTC).
Example: "1509029215" ≡ 26-Oct-2017 14:46:55 CEST
5.9.4.4.4.5 .surveillance.errorTable.errorEntry.errorPending
OID: .1.3.6.1.4.1.21035.41.3.4.1.5.x
Syntax: INTEGER {pending (1), gone (2)}
Access: read-only
Description: The last occurrence of the event is
"1" still pending, or
"2" not pending anymore, i.e. gone.
5.9.4.4.4.6 .surveillance.errorTable.errorEntry.errorAcknowledge
OID: .1.3.6.1.4.1.21035.41.3.4.1.6.x
Syntax: INTEGER {notAcknowledged (1), acknowledged (2)}
Access: read-only
Description: The last occurrence of the event is
"1" not acknowledged, or
"2" acknowledged.
5.9.4.4.5 .surveillance.numberOfPowerLines
OID: .1.3.6.1.4.1.21035.41.3.5.0
Syntax: INTEGER32
Access: read-only
Description: The number of power lines. This type of device does not support
monitoring for the power lines, thus "0" is returned.
Note:
This value is used to determine the maximum index of the following table:
5.9.4.4.6 .surveillance.powerLineTable
The .powerLineTable is required for products that support power line monitoring,
i.e. it is not relevant for this type of device. Therefore and due to the fact that for
.numberOPowerLines (please refer to chapter 5.9.4.4.5) "0" is returned, the
.powerLineTable is not available.
5.9.4.4.6.1 .surveillance.powerLineTable.powerLineEntry.powerLineIndex
OID: .1.3.6.1.4.1.21035.41.3.6.1.1.x
Syntax: INTEGER32 (1..3)
Access: not-accessible
Description: A unique value for each table entry ranging between "1" and the
number of entries (defined by .numberOfPowerLines, please refer
to chapter 5.9.4.4.5 ). Not applicable for this type of device, since
the .powerLineTable is not available.