20 ECY-303 Preloaded Applications
ID Units Valid Range Default Value
Analog Value 21 Percent (%) 0 to 100% 999%
Dampers (AV22)
This variable is used to display the actual outside air dampers signal. This variable can be used to
override the outside air dampers control signal.
ID Units Valid Range Default Value
Analog Value 22 Percent (%) 0 to 100% 999%
OptStartMaxStartupTime (AV23)
This variable is used to configure the maximum startup time allowed before the occupied mode.
ID Units Valid Range Default Value
Analog Value 23 minutes N/A 240 min
OptStartFactorWeight (AV24)
This variable is used to configure the % of the new factor that will be taken into account to calculate
the new factor OptStartCoolFactor (AV14) or OptStartHeatFactor (AV15).
ID Units Valid Range Default Value
Analog Value 24 Percent (%) 1 to 100% 10%
CoolStgOnDelay (AV26)
This variable is used to configure the delay before starting any cooling stage.
ID Units Valid Range Default Value
Analog Value 26 Seconds N/A 180s
CoolStgOffDelay (AV27)
This variable is used to configure the delay before stopping any cooling stage.
ID Units Valid Range Default Value
Analog Value 27 Seconds N/A 120s
HeatStgOnDelay (AV28)
This variable is used to configure the delay before starting any heating stage.
ID Units Valid Range Default Value
Analog Value 28 Seconds N/A 180s
HeatStgOffDelay (AV29)
This variable is used to configure the delay before stopping any heating stage.
ID Units Valid Range Default Value
Analog Value 29 Seconds N/A 120s
DampersDischAirSP (AV30)
This variable is used to configure the minimum discharge temperature limit for the outside air dampers
control signal.