22 ECY-303 Preloaded Applications
ID Units Valid Range Default Value
Analog Value 37 Degrees-Celsius (°C) N/A N/A
UnoccCoolSp (AV38)
This variable is used to configure the cooling setpoint when the occupancy status (MSV15) is in unoc-
cupied mode.
ID Units Valid Range Default Value
Analog Value 38 Degrees-Celsius (°C) N/A 28°C
StandbyCoolSp (AV39)
This variable is used to configure the cooling setpoint when the occupancy status (MSV15) is in
standby mode.
ID Units Valid Range Default Value
Analog Value 39 Degrees-Celsius (°C) N/A 26°C
OccCoolSp (AV40)
This variable is used to configure the cooling setpoint when the occupancy status (MSV15) is in occu-
pied mode.
ID Units Valid Range Default Value
Analog Value 40 Degrees-Celsius (°C) N/A 24°C
OccHeatSp (AV41)
This variable is used to configure the heating setpoint when the occupancy status (MSV15) is in occu-
pied mode.
ID Units Valid Range Default Value
Analog Value 41 Degrees-Celsius (°C) N/A 21°C
StandbyHeatSp (AV42)
This variable is used to configure the heating setpoint when the occupancy status (MSV15) is in
standby mode.
ID Units Valid Range Default Value
Analog Value 42 Degrees-Celsius (°C) N/A 19°C
UnoccHeatSp (AV43)
This variable is used to configure the heating setpoint when the occupancy status (MSV15) is in unoc-
cupied mode.
ID Units Valid Range Default Value
Analog Value 43 Degrees-Celsius (°C) N/A 17°C
MinFanCurrent (AV44)
This variable is used to configure the minimum scaling of UI6 when configured for FanCurrent. The
range of the input can be configured using UI6Range(MSV20)
ID Units Valid Range Default Value
Analog Value 44 Amperes (A) N/A 0 A
Variables