EasyManua.ls Logo

Eaton easyE4

Eaton easyE4
879 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. easyE4 communication Connection to other devices
10.17 Modbus TCP
The value range is 1 to 65535. The default is ID 1.
As specified in the Modbus specification, the start address of a data packet minus 1
(address offset) will be transferred.
Older devices still use this address range and will interpret the transmitted address
with an offset of +1.
On newer devices, such as easyE4 devices, addresses start from start address 0
instead.
If you want to configure Modbus communications with a Modbus server/slave for the
easyE4 base device and the corresponding addresses start from start address 0, then
the Auto-decrement on all addresses option must be disabled. The Modbus cli-
ent's/master's address will be sent without any additional conversion steps and the
address will be the exact same on the Modbus server/slave.
If you want to configure Modbus communications with a Modbus server/slave for the
easyE4 base device and the corresponding addresses start from start address 1, then
you will need to enable the Auto-decrement on all addresses option for the Modbus
server/slave. To ensure that addresses are used correctly, an offset bit of 1 will be
subtracted from all the addresses for the Modbus client/master.
If the Auto-decrement on all addresses option were disabled, the easyE4 would, for
example, send address 1 so that address 2 on the Modbus map would be selected for
the Modbus server/slave if the latter were a device for which addresses start with
start address 1.
easyE402/24 MN050009ENEaton.com
781

Table of Contents

Other manuals for Eaton easyE4

Related product manuals