List of event codes
Information – 249
635 Critical Battery temperature low critical Batterytemperature OK Check battery
637 Critical Batterytemperature high critical Battery temperature OK Check battery
63E Critical Battery fault Battery OK Check battery
704 Critical Inverter internal failure UPS OK Service required
705 Critical Inverter overload No power overload Reduce output load
706 Critical Temperature alarm Temperature OK Check air conditioner
70B Critical Inverter short circuit End of inverter short circuit Service required
805 Critical Output short circuit Output OK Reduce output load
811 Critical Parallel negative power Parallel power OK Reduce output load
815 Critical Calibration fault Calibration OK Service required
81E Critical Load unprotected Load protected -
7.5.2.2 Warning
Code Severity Active message Non-active message Advice
001 Warning On battery No more on battery -
007 Warning Fan fault Fan OK Service required
00B Warning Parallel UPS redundancy lost Parallel UPS redundancy OK Reduce output load
00E Warning Parallel UPS communication lost Parallel UPS communication OK Service required
00F Warning Parallel UPS not compatible Parallel UPS compatibility OK Service required
010 Warning UPS power supply fault UPS power supply OK Service required
011 Warning Parallel UPS protection lost Parallel UPS protection OK Reduce output load
012 Warning Parallel UPS measure inconsistent Parallel UPS measure OK Service required
020 Warning On battery On normal mode
021 Warning On bypass On normal mode
022 Warning Alarm signaled No alarm reported -
103 Warning Utility breaker open Utility breaker closed -
104 Warning Input AC frequency out of range Input AC frequency in range -
106 Warning Input AC not present Input AC present -
107 Warning Input bad wiring Input wiring OK Check input wiring
108 Warning Input AC voltage out of range (-) Input AC voltage in range -
109 Warning Input AC voltage out of range (+) Input AC voltage in range -