SNMP traps
Information – 268
Trap oid :
.1.3.6.1.4.1.534.1.11
.4.1.0.x
Trap message at
oid :
.1.3.6.1.4.1.534.1.1
1.3.0
Code HID (For UPS 5P, 5PX, 9SX,
9PX, 9xPM, 9xE, 9xPS)
Code XCP (For UPS Blade,
9395, 9395P, 9395C, 9x55)
.1.3.6.1.4.1.534.1.11
.4.1.0.43
Sensor humidity is
below/above critical
threshold
.1.3.6.1.4.1.534.1.11
.4.1.0.48
Maintenance
bypass
900 2143
.1.3.6.1.4.1.534.1.11
.4.1.0.52
Charger voltage
alarm
502, 503 2023, 2116
.1.3.6.1.4.1.534.1.11
.4.1.0.53
Short circuit 308, 629, 70B, 805
7.6.2 ATS Mib
This information is for reference only.
Trap oid :
.1.3.6.1.4.1.534.10.2.10.x
Trap description
.1.3.6.1.4.1.534.10.2.10.1 Communication lost
.1.3.6.1.4.1.534.10.2.10.2 Communication recovered
.1.3.6.1.4.1.534.10.2.10.3 Output powered
.1.3.6.1.4.1.534.10.2.10.4 Output not powered
.1.3.6.1.4.1.534.10.2.10.5 Overload
.1.3.6.1.4.1.534.10.2.10.6 No overload
.1.3.6.1.4.1.534.10.2.10.7 Internal failure
.1.3.6.1.4.1.534.10.2.10.8 No internal failure
.1.3.6.1.4.1.534.10.2.10.9 Source 1 normal
.1.3.6.1.4.1.534.10.2.10.10 Source 1 out of range
.1.3.6.1.4.1.534.10.2.10.11 Source 2 normal
.1.3.6.1.4.1.534.10.2.10.12 Source 2 out of range
.1.3.6.1.4.1.534.10.2.10.13 Sources desynchronized
.1.3.6.1.4.1.534.10.2.10.14 Sources synchronized
.1.3.6.1.4.1.534.10.2.10.15 Output powered by source 1
.1.3.6.1.4.1.534.10.2.10.16 Output powered by source 2
.1.3.6.1.4.1.534.10.2.10.20 Remote temperature low
.1.3.6.1.4.1.534.10.2.10.21 Remote temperature high