Information – 265
7.5.6.2.2 Communication
Code Severity Active message Non-active message Advice
1300 Info Communication: No device connected Communication: Communication with the device is back -
1301 Info Communication: Device not supported Communication: Communication with the device is back -
7.5.6.2.3 Alarms
Code Severity Active message Non-active message Advice
1302 Info Alarms: the number of alarms is
high and above 5 000
Alarms: the number of alarms is
back to normal
It is recommended to
Export and Clear the alarm
log.
7.6 SNMP traps
7.6.1 UPS Mib
7.6.1.1 IETF Mib-2 Ups traps
This information is for reference only.
Trap oid :
.1.3.6.1.2.1.33.2.0.x
Description :
.1.3.6.1.2.1.33.2.0.1 Sent whenever the UPS transfers on battery,
then sent every minutes until the UPS Comes back to AC Input.
.1.3.6.1.2.1.33.2.0.3 Sent whenever an alarm appears.
The matching alarm oid is added as bound variables in the table below.
.1.3.6.1.2.1.33.2.0.4 Sent whenever an alarm disappears.
The matching alarm oid is added as bound variables in the table below.
Alarm oid at :
.1.3.6.1.2.1.33.1.6.3.x
Description when trap 3 Description when trap 4
.1.3.6.1.2.1.33.1.6.3.1 Battery test failed Battery test OK
.1.3.6.1.2.1.33.1.6.3.2 Battery discharging End of UPS battery discharge
.1.3.6.1.2.1.33.1.6.3.3 Low battery Battery OK
.1.3.6.1.2.1.33.1.6.3.5 Temperature alarm Temperature OK
.1.3.6.1.2.1.33.1.6.3.6 Input AC not present Input AC present