EasyManua.ls Logo

Eaton Network-M3 - UPS(XCP and COPI) Alarm Log Codes

Eaton Network-M3
294 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of event codes
Information – 254
7.5.3 UPS(XCP and COPI) alarm log codes
7.5.3.1 Critical
Code Severity Active message Non-active message Advice
2002 Critical Inverter AC frequency out of range Inverter AC frequency in range -
2012 Critical Emergency power OFF No emergency OFF -
2020 Critical Bypass temperature alarm Bypass temperature OK -
2022 Critical Charger power supply tripped Charger power supply no longer
tripped
-
2024 Critical Inverter Temperature too high Inverter Temperature OK -
2026 Critical Rectifier current too high Rectifier OK -
2030 Critical Rectifier failure Rectifier current OK -
2031 Critical Inverter internal failure UPS OK -
2032 Critical Battery breaker failure Battery breaker OK -
2033 Critical Automatic bypass breaker failure Automatic bypass breaker OK -
2034 Critical Battery charger fault Battery charger OK -
2036 Critical Bypass AC static switch failure Bypass AC static switch OK -
2246 Critical Neutral current limitation Neutral current OK -
2048 Critical Inverter Start failure Inverter Start OK -
2051 Critical Battery ground fault Battery ground OK -
2053 Critical Non volatile memory failure Non volatile memory OK -
2055 Critical UPS shutdown imminent UPS shutdown no longer imminent -
2056 Critical Battery low state of charge Battery state of charge OK -
2058 Critical Output short circuit Output OK -
2064 Critical Rectifier self test failed Rectifier self test OK -
2068 Critical Battery voltage too high Battery voltage OK -
Use this table for 9130, 9x55, 9395P, BladeUPS.
To retrieve Alarm logs, navigate to Contextual help>>>Alarms section and press the Download alarms button.
Below codes are the one to be used to add "Exceptions on events notification" on email sending configurations.
Some zeros maybe added in front of the code when displayed in emails or logs.

Table of Contents